Analog electronics modules<br />

4.21 2AO I Standard analog electronic module (6ES7135-4GB01-0AB0)<br />

Suppression of interference, limits of error<br />

Crosstalk between the outputs min. -40 dB<br />

Operational limit (in the entire temperature<br />

range, with reference to the output range)<br />

± 0.5 %<br />

Basic error limit (operational limit at 25 °C<br />

with reference to output range)<br />

± 0.3 %<br />

Temperature error (with reference to the<br />

output range)<br />

± 0.01 %/K<br />

Linearity error (with reference to the output<br />

range)<br />

± 0.02 %<br />

Repeatability<br />

(in steady state at 25 °C with reference to<br />

output range)<br />

± 0.05 %<br />

Output ripple (with reference to output range,<br />

bandwidth 0 to 50 kHz)<br />

± 0.02 %<br />

Output range (rated value)<br />

Data for selecting an actuator<br />

± 20 mA<br />

4 to 20 mA<br />

Load resistance max. 500 Ω<br />

• For inductive load 1 mH<br />

• Open circuit voltage 18 V<br />

Destruction limit against voltages/currents<br />

applied from outside<br />

• Voltage at the outputs to MANA 15 V continuous; 75 V for max. 1 ms<br />

(sampling ratio 1:20)<br />

• Current max. 50 mA DC<br />

Connection of actuators<br />

• Two-wire connection Yes<br />

• Four-wire connection no<br />

<strong>ET</strong> <strong>200S</strong><br />

Manual, 12/2005, A5E00514527-03 4-109