Analog electronics modules<br />

4.11 2AI I 2WIRE High Speed analog electronic module (6ES7134-4GB51-0AB0)<br />

Cable length<br />

• Shielded max. 200 m<br />

Parameter length 12 bytes<br />

(4 bytes when used as 6ES7134 4FB50 0AB0)<br />

Voltages, currents, potentials<br />

Rated load voltage L+ (from the power module) 24 VDC<br />

• Reverse polarity protection Yes<br />

• Short-circuit protection Yes, (destruction limit 35 mA per channel)<br />

Galvanic isolation<br />

• Between channels and backplane bus Yes<br />

• Between channels and load voltage L+ no<br />

• Between the channels no<br />

Permissible potential difference<br />

• Between MANA and Minternal (UISO) 75 VDC, 60 VAC<br />

Insulation test voltage 500 VDC<br />

Current consumption<br />

• Supply and load voltage L+ max. 35 mA 1<br />

Power dissipation of the module Typically 0.8 W<br />

Interrupts<br />

Status, interrupts, diagnostics<br />

• Hardware interrupt Can be assigned parameters 2<br />

Diagnostics function<br />

• Group error display Red "SF" LED<br />

• Diagnostic functions readable Possible 3<br />

Analog value generation<br />

Measuring principle Instantaneous value encoding<br />

Cycle time/resolution:<br />

• Conversion time in ms (per channel) 0.1<br />

• Cycle time in ms (per module) 1<br />

• Resolution (including overrange) 4 mA to 20 mA/13 bits<br />

0 mA to 20 mA/13 bits<br />

Crosstalk between the inputs<br />

Suppression of interference, limits of error<br />

> 50 dB<br />

Operational limit<br />

±0.3%<br />

(in the entire temperature range, with reference to<br />

the input range)<br />

Basic error limit (operational limit at 25° C with<br />

reference to input range)<br />

± 0.2%<br />

Temperature error (with reference to the input<br />

range)<br />

± 0.01 %/K<br />

Linearity error (with reference to the input range) ± 0.01%<br />

Repeatability<br />

(in steady state at 25° C with reference to input<br />

range)<br />

± 0.05%<br />

Sensor power supply outputs<br />

<strong>ET</strong> <strong>200S</strong><br />