Analog electronics modules<br />

4.5 Parameters for analog electronic modules<br />

See also<br />

Connecting Thermocouples (Page 4-19)<br />

4.5.2 Parameters for analog electronic modules 2AI U High Feature and 2AI I 2/4WIRE<br />

High Feature<br />

Table 4-31 Parameters for analog electronic modules U, I High Feature<br />

2AI U High Feature 2AI I 2/4WIRE High Feature Range of values Default setting Applicability<br />

Group diagnosis (parameter assignment error, • disable<br />

disable Module<br />

internal error)<br />

• Enable<br />

Diagnostics: Overflow/underflow • disable<br />

disable Module<br />

• Enable<br />

--- Diagnostics: Wire break1 • disable<br />

disable Channel<br />

• Enable<br />

Smoothing • None<br />

None Channel<br />

• Weak<br />

• Medium<br />

• Strong<br />

Type/range of --- • De-activated<br />

± 10 V Channel<br />

measurement<br />

• ± 5 V<br />

• 1 V to 5 V<br />

• ± 10 V<br />

--- Type/range of measurement • De-activated<br />

4 to 20 mA Channel<br />

• 4 to 20 mA<br />

• ± 20 mA<br />

Interference frequency suppression • disable<br />

disable Module<br />

• Enable<br />

Run-time calibration • disable<br />

disable Module<br />

1 Only in the measuring range 4 to 20 mA<br />

• Enable<br />

See also<br />

Connecting Thermocouples (Page 4-19)<br />

<strong>ET</strong> <strong>200S</strong><br />

4-28 Manual, 12/2005, A5E00514527-03