Digital electronic modules<br />

3.20 2RO NO/NC 24 VDC to 48 VDC/5 A, 24 VAC to 230 VAC/5 A digital electronic module (6ES7132-4HB10-0AB0)<br />

Status display<br />

Status, interrupts, diagnostics<br />

Green LED per channel<br />

Diagnostics function<br />

Output current<br />

no<br />

Data for selecting an actuator<br />

• Continuous thermal current max. 5 A<br />

• Min. load current 8 mA<br />

Connecting two outputs in parallel<br />

• for redundant triggering of a load no<br />

• To increase performance no<br />

Control of a digital input<br />

Switch rate<br />

Yes<br />

• For resistive load 2 Hz<br />

• On inductive load 0.5 Hz<br />

• For lamp load 2 Hz<br />

Limitation (internal) of the voltage induced on<br />

circuit interruption<br />

no<br />

Short-circuit protection of the output 1 no<br />

1 The relay outputs must be fused externally with 6 A. For installation in a hazardous area as<br />

specified by the National Electric Code (NEC) the fuse must only be removed with a suitable tool if<br />

the subassembly is not in an explosive area.<br />

<strong>ET</strong> <strong>200S</strong><br />

Manual, 12/2005, A5E00514527-03 3-85