Analog electronics modules<br />

4.15 2AI RTD Standard analog electronic module (6ES7134-4JB50-0AB0)<br />

4.15 4.15<br />

Properties<br />

Maximum input current for current input 60 mA<br />

(destruction limit)<br />

Smoothing of the measured values Yes, can be assigned parameters in 4 steps by means<br />

of digital filtering<br />

Step<br />

Time constant<br />

None<br />

1 x cycle time<br />

Weak<br />

64 x cycle time<br />

Medium<br />

128 x cycle time<br />

Strong<br />

512 x cycle time<br />

1 Without encoder supply voltage<br />

2 DPV1 only<br />

3 Parameter assignment error<br />

Violation of lower limit value<br />

Violation of upper limit value<br />

Open circuit (only with 4 mA to 20 mA)<br />

Process interrupt lost<br />

2AI RTD Standard analog electronic module (6ES7134-4JB50-0AB0)<br />

General terminal assignment<br />

• 2 inputs for resistance thermometers or resistance measurement<br />

• Input ranges:<br />

– Resistance thermometers: Pt100, Ni100; resolution 15 bits + sign<br />

– Resistance measurement: 150 Ω; 300 Ω ; 600 Ω, resolution max. 15 bits + sign<br />

• Isolated from the load voltage L+<br />

• Linearization of the sensor characteristic curves<br />

Note<br />

Terminals 4, 8, A4, A8, A3 and A7 are only available at specified terminal modules.<br />

The resistance thermometers/resistors are measured in a four-wire connection. Constant<br />

current is fed to the resistance thermometers/resistors by means of connections IC+ and IC-.<br />

The voltage measured at the resistance thermometer/resistor is measured at the<br />

connections M+ and M-. This ensures highly accurate measurement results with the fourwire<br />

connection.<br />

With the two/three-wire connection, you must apply corresponding jumpers to the module<br />

between M+ and Ic+ or M- and Ic- . However, you have to expect a loss of accuracy in the<br />

measurement results.<br />