Analog electronics modules<br />

4.2 Analog value representation<br />

Measuring ranges for resistance thermometer Ni x00 Climatic<br />

Table 4-11 SIMATIC S7 format: Measuring ranges Ni 100, 120, 200, 500, 1000 Climatic in °C and °F<br />

Ni x00 Climatic in °C<br />

Units Ni x00 Climatic in °F<br />

Units<br />

(1 digit = 0.01 °C) Decimal Hexadecimal (1 digit = 0.01 °F) Decimal Hexadeci<br />

mal<br />

> 295.00 32767 7FFFH > 325.11 32767 7FFFH Overflow<br />

295.00<br />

:<br />

29500<br />

:<br />

733CH<br />

:<br />

327.66<br />

Range<br />

250.01<br />

25001 61A9H<br />

280.01<br />

28001 6D61H<br />

250.00<br />

25000 61A8H<br />

280.00<br />

28000 6D60H<br />

:<br />

:<br />

:<br />

:<br />

:<br />

: Rated range<br />

-60.00<br />

-6000 E890H<br />

-76.00<br />

-7600 E250H<br />

-60.01<br />

-6001 E88FH<br />

-76.01<br />

-7601 E24FH<br />

:<br />

:<br />

:<br />

:<br />

:<br />

: Undershoot<br />

-105.00<br />

-10500 D6FCH<br />

-157.00<br />

-15700 C2ACH range<br />

< -105.00 -32768 8000H < -157.00 -32768 8000H Underflow<br />

Measuring ranges for resistance thermometer Cu 10 Standard<br />

Table 4-12 SIMATIC S7 format: Measuring ranges Cu 10 Standard in °C and °F<br />

<strong>ET</strong> <strong>200S</strong><br />

4-8 Manual, 12/2005, A5E00514527-03<br />

:<br />

32766<br />

:<br />

7FFEH<br />

:<br />

Overshoot range<br />

Cu 10 Standard in °C<br />

Units Cu 10 Standard in °F<br />

Units<br />

Range<br />

(1 digit = 0.1 °C) Decimal Hexadecimal (1 digit = 0.1 °F) Decimal Hexadeci<br />

mal<br />

> 312.0 32767 7FFFH > 593.6 32767 7FFFH Overflow<br />

312.0<br />

3120 C30H<br />

593.6<br />

5936 1730H<br />

:<br />

:<br />

:<br />

:<br />

:<br />

: Overshoot range<br />

260.1<br />

2601 A29H<br />

500.1<br />

5001 12D5H<br />

260.0<br />

2600 A28H<br />

500.0<br />

5000 1389H<br />

:<br />

:<br />

:<br />

:<br />

:<br />

: Rated range<br />

-200.0<br />

-2000 F830H<br />

-328.0<br />

-3280 F330H<br />

-200.1<br />

-2001 F82FH<br />

-328.1<br />

-3281 F32FH<br />

:<br />

:<br />

:<br />

:<br />

:<br />

: Undershoot<br />

-240.0<br />

-2400 F6A0H<br />

-400.0<br />

-4000 F060H range<br />

< -240.0 -32768 8000H < -400.0 -32768 8000H Underflow