Analog electronics modules<br />

4.21 2AO I Standard analog electronic module (6ES7135-4GB01-0AB0)<br />

4.21 4.21<br />

Properties<br />

2AO I Standard analog electronic module (6ES7135-4GB01-0AB0)<br />

General terminal assignment<br />

• 2 outputs for current output<br />

• Output range:<br />

– ± 20 mA, resolution 13 bits + sign<br />

– 4 to 20 mA, resolution 13 bits<br />

• Isolated from the load voltage L+<br />

Note<br />

Terminals 4, 8, A4, A8, A3 and A7 are only available at specified terminal modules.<br />

Terminal assignment for 2AO I Standard (6ES7135-4GB01-0AB0)<br />

Terminal Assignment Terminal Assignment Notes<br />

1 QI0 5 QI1 • QIn: Current analog output, channel n<br />

2 n.c. 6 n.c. • Mana: Ground of the module<br />

3 Mana 7 Mana • n.c.: Not connected (max. DC 30 V can be connected)<br />

4<br />

A4<br />

n.c.<br />

AUX1<br />

8<br />

A8<br />

n.c.<br />

AUX1<br />

• AUX1: Protective-conductor terminal or potential bus (freely usable<br />

up to 230 VAC)<br />

A3 AUX1 A7 AUX1<br />

<strong>ET</strong> <strong>200S</strong><br />