Analog electronics modules<br />

4.14 2AI I 4WIRE High Speed analog electronic module (6ES7134-4GB61-0AB0)<br />

Status, interrupts, diagnostics<br />

Interrupts<br />

• Hardware interrupt Can be assigned parameters2 Diagnostics function<br />

• Group error display Red "SF" LED<br />

• Diagnostic information readable Possible3 Analog value generation<br />

Measuring principle<br />

Cycle time/resolution:<br />

Instantaneous value encoding<br />

• Conversion time in ms (per channel) 0.1<br />

• Cycle time in ms (per module) 1<br />

• Resolution (including overrange) 4 mA to 20 mA/13 bit<br />

0 mA to 20 mA/13 bit<br />

± 20 mA/13 bits + sign<br />

Crosstalk between the inputs<br />

Suppression of interference, limits of error<br />

> 50 dB<br />

Operational limit<br />

± 0.3 %<br />

(in the entire temperature range, with<br />

reference to the input range)<br />

Basic error limit (operational limit<br />

at 25 °C with reference to input range)<br />

± 0.2 %<br />

Temperature error (with reference to the<br />

input range)<br />

± 0.01 %/K<br />

Linearity error (with reference to the input<br />

range)<br />

± 0.01 %<br />

Repeatability<br />

(in steady state at 25° C with reference to<br />

input range)<br />

± 0.05 %<br />

Number of outputs<br />

Output voltage<br />

Sensor power supply outputs<br />

2<br />

• With load<br />

L+ (-2.5 V)<br />

Output current<br />

• Rated value<br />

90 mA (both channels)<br />

• Permitted range<br />

0 mA to 90 mA<br />

Short-circuit protection Yes, electronic<br />

Data for selecting a sensor<br />

Input range (rated value)/input resistance<br />

• Current 4 mA to 20 mA/50 Ω<br />

0 mA to 20 mA/50 Ω<br />

± 20 mA/50 Ω<br />

Connection of the sensors<br />

• For current measurement as two-wire<br />

transmitter<br />

supported<br />

Load of the two-wire measuring transducer max. 670 Ω<br />

<strong>ET</strong> <strong>200S</strong><br />

Manual, 12/2005, A5E00514527-03 4-73