3.8 3.8<br />

Characteristics<br />

Digital electronic modules<br />

3.8 4DI 24 VUC to 48 VUC High Feature digital electronic module (6ES7131-4CD00-0AB0)<br />

Data for selecting a sensor<br />

Input voltage<br />

• Rated value 24 V DC<br />

• For signal "1" 11 to 30 V<br />

• For signal "0" -30 to 5 V<br />

Input current<br />

• With "1" signal<br />

Typ. 8 mA<br />

Input delay (parameters can be assigned)<br />

• At "1" after "0" 0.1 ms (0.05 to 0.15 ms)<br />

0.5 ms (0.4 to 0.6 ms)<br />

3 ms (2.7 to 3.3 ms)<br />

15 ms (14.85 to 15.15 ms)<br />

• At "1" after "0" 0.1 ms (0.05 to 0.15 ms)<br />

0.5 ms (0.4 to 0.6 ms)<br />

3 ms (2.7 to 3.3 ms)<br />

15 ms (14.85 to 15.15 ms)<br />

Input characteristic curve According to IEC 61131, Type 1<br />

Connection of 2-wire BEROs Supported<br />

• Permitted quiescent current max. 1.5 mA<br />

1 Per module<br />

4DI 24 VUC to 48 VUC High Feature digital electronic module<br />

(6ES7131-4CD00-0AB0)<br />

General terminal assignment<br />

• Digital electronics module with four inputs<br />

• Rated input voltage 24 VAC/VDC to 48 VAC/VDC<br />

• Diagnostics: Wire break<br />

• Diagnostics: Fuse blown<br />

• Diagnostics: Missing load voltage<br />

• Suitable for switches and proximity switches (BEROs)<br />

• Supports isochronous operation<br />

Note<br />

Terminals 4, 8, A4, A8, A3 and A7 are only available at specified terminal modules.<br />

<strong>ET</strong> <strong>200S</strong><br />

Manual, 12/2005, A5E00514527-03 3-27