3.9 3.9<br />

Properties<br />

Digital electronic modules<br />

3.9 4DI NAMUR digital electronic module (6ES7131-4RD00-0AB0)<br />

Sensor switching<br />

Resistance circuit of the sensor for wire break<br />

monitoring<br />

• Nominal voltage<br />

24 V (15 V to 35 V)<br />

18 kΩ<br />

• Nominal voltage<br />

48 V (30 V to 60 V)<br />

39 kΩ<br />

1 IEC 61131 does not provide technical specifications for UC modules. However, the values have<br />

been adjusted to IEC 61131 as closely as possible.<br />

2 Minimum load current is required in the case of wire-break monitoring.<br />

4DI NAMUR digital electronic module (6ES7131-4RD00-0AB0)<br />

General terminal assignment<br />

• Digital electronics module with four inputs<br />

• Encoder power supply 8.2 VDC<br />

• Suitable for NAMUR sensors and both closed and open mechanical contacts<br />

Note<br />

Terminals 4, 8, A4, A8, A3 and A7 are only available at specified terminal modules.<br />

Terminal assignment of the 4DI NAMUR (6ES7131-4RD00-0AB0)<br />

Terminal Assignment Terminal Assignment Notes<br />

1 DI0 5 DI1 • DIn: Input signal, channel n<br />

2 DI2 6 DI3 • VS: Encoder power supply 8.2 VDC<br />

3<br />

4<br />

VS<br />

VS<br />

7<br />

8<br />

VS<br />

VS<br />

• AUX1: Protective-conductor terminal or potential bus (freely usable<br />

up to 230 VAC)<br />

A4 AUX1 A8 AUX1<br />

A3 AUX1 A7 AUX1<br />

<strong>ET</strong> <strong>200S</strong><br />

Manual, 12/2005, A5E00514527-03 3-31