Analog electronics modules<br />

4.5 Parameters for analog electronic modules<br />

4.5.5 Parameters for 2AI RTD High Feature analog electronic module<br />

Table 4-34 Parameters for 2AI RTD High Feature analog electronic module<br />

Parameters Range of values Default setting Applicability<br />

Group diagnostics • Disable<br />

Disable Module<br />

• Enable<br />

Diagnostics:<br />

• Disable<br />

Disable Module<br />

overflow/underflow<br />

• Enable<br />

Diagnostics: Wire break • Disable1 Disable Channel<br />

• Enable<br />

Smoothing • None<br />

None Channel<br />

• Weak<br />

• Medium<br />

• Strong<br />

Temperature unit • Celsius<br />

Celsius Module<br />

• Fahrenheit<br />

Type of measurement • De-activated<br />

Four-wire thermal Channel<br />

• Four-wire resistor<br />

resistor<br />

• Three-wire resistor<br />

• Two-wire resistor<br />

• Four-wire thermal resistor<br />

• Three-wire thermal resistor<br />

• Two-wire thermal resistor<br />

Temperature coefficient • Pt 0.003850<br />

Pt 0.003851 Channel<br />

• Pt 0.003916<br />

• Pt 0.003902<br />

• Pt 0.003920<br />

• Pt 0.003851<br />

• Ni 0.006180<br />

• Ni 0.006720<br />

• Ni 0.005000<br />

• Cu 0.00427<br />

Measuring range • 150 Ω<br />

Pt100 Standard Channel<br />

• 300 Ω<br />

• 600 Ω<br />

• 3000 Ω<br />

• PTC<br />

• Pt100 Climatic<br />

• Ni100 Climatic Range<br />

• Pt100 Standard<br />

• Ni100 Standard<br />

• Pt500 standard range<br />

• Pt1000 standard range<br />

• Ni1000 standard range<br />

• Pt200 climatic range<br />

• Pt500 climatic range<br />

<strong>ET</strong> <strong>200S</strong><br />