01.06.2013 Views

Distributed I/O System ET 200S

Distributed I/O System ET 200S

Distributed I/O System ET 200S

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

I&M functions<br />

New Information About the "<strong>ET</strong> <strong>200S</strong> <strong>Distributed</strong> I/O <strong>System</strong> Manual"<br />

3.6 2AO I High Feature Analog Electronic Module (6ES7135-4MB02-0AB0)<br />

Reading of the I&M data from the module is possible with interface modules as from a higher<br />

order number (MLFB) or as from a higher firmware/product version than described in the<br />

following table:<br />

Interface module Order no. Firmware version Product version<br />

IM151-1 HIGH FEATURE 6ES7151-1BA01-0AB0 V2.0 02<br />

IM151-3 PN 6ES7151-3AA20-0AB0 V4.0 01<br />

IM151-3 PN HIGH FEATURE 6ES7151-3BA20-0AB0 V4.0 01<br />

IM151-3 PN FO 6ES7151-3BB21-0AB0 V4.0 01<br />

Note<br />

Use of the module after an IM151-7 CPU<br />

If the module is positioned after an IM151-7 CPU, it outputs the last values before a RUN-<br />

STOP transition, provided no values were output by the user program after the STOP-RUN<br />

transition.<br />

Take this into account when programming the start-up of the control function (OB100 or<br />

OB1).<br />

<strong>ET</strong> <strong>200S</strong><br />

Product Information, 12/2006, A5E00743001-02 3-21

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!