Power modules<br />

2.2 Parameters for power modules<br />

Status byte power modules<br />

2.2 2.2<br />

Parameters<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Figure 2-1 Assignment of status byte for power modules<br />

Parameters for power modules<br />

The following table lists the power module parameters.<br />

Table 2-2 Parameters for power modules<br />

Power module<br />

PM-E DC24V PM E-<br />

24 ..48 VDC<br />

Diagnostics:<br />

Missing load<br />

voltage<br />

Diagnostics:<br />

Missing load<br />

voltage<br />

PM-E 24 to 48 VDC/<br />

24 to 230 VAC 1<br />

Diagnostics: Missing<br />

load voltage<br />

Value range Default setting Applicability<br />

Disable/enable Disable Power module<br />

--- --- Diagnostics: Fuse Disable/enable Disable Power module<br />

blown<br />

--- --- Voltage type DC/AC DC Power module<br />

1 The PM-E 24 VDC to 48 VDC, 24 VAC to 230 VAC power module (6ES7138-4CB11-0AB0) is not a direct replacement<br />

for the device with the order number 6ES7138-4CB00-0AB0 for AC applications because you have to select either AC or<br />

DC supply voltage. In the case of DC applications, the new module is a direct replacement because the default setting of<br />

the new parameter is "DC". If you want to replace the device 6ES7138-4CB00-0AB0 in AC applications, you have to create<br />

a new hardware configuration and set the value "AC" for the load voltage type parameter.<br />

Here is a more detailed explanation of the parameters.<br />

<strong>ET</strong> <strong>200S</strong><br />

2-2 Manual, 12/2005, A5E00514527-03

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!