Analog electronics modules<br />

4.4 Response of the analog modules during operation and if faults occur<br />

4.4.2 Influence of the Value Range on the Analog Input<br />

The response of the electronics modules with analog inputs depends on the part of the value<br />

range in which the input values are located. The table below shows this dependency..<br />

Table 4-28 Response of the Analog Modules, Depending on the Location of the Analog Input Value in the Range of<br />

Values<br />

Measured value within ... Input value in SIMATIC S7 Format Input value in SIMATIC S5 Format<br />

Rated range Measured value Measured value<br />

Overshoot/undershoot range Measured value Measured value<br />

Overflow 7FFFH End of overshoot range +1 plus<br />

overflow bit<br />

Underflow 8000H End of undershoot range -1 plus<br />

overflow bit<br />

Before setting parameters or with faulty<br />

parameters 1<br />

7FFFH 7FFFH<br />

1 With 2AI U Standard, 2AI I 2WIRE Standard, 2AI I 4WIRE Standard, 2AI RTD Standard, 2AI TC Standard with product<br />

status 1 applies: If the parameter setting error diagnostics message is triggered because of incorrect parameter setting<br />

(e.g. wire break in measuring range ± 20 mA), the SF LED on the module lights and the diagnosis can be evaluated. In this<br />

status correct input values are sent to the DP master.<br />

4.4.3 Influence of the Value Range on the Analog Output<br />

The response of the electronics modules with analog outputs depends on the part of the<br />

value range in which the output values are located. The table below shows this dependency..<br />

Table 4-29 Response of the Analog Modules, Depending on the Location of the Analog Output Value in the Range of<br />

Values<br />

Output Value is in ... Input value in SIMATIC S5/S7 format<br />

Rated range Value from DP master<br />

Overshoot/undershoot range Value from DP master<br />

Overflow 0-signal<br />

Underflow 0-signal<br />

Before setting parameters or with faulty parameters1 0-signal<br />

1 With 2AO U Standard, 2AO I Standard with product status 1 applies: If the configured substitute value is outside the<br />

nominal range, a diagnostics message for a parameter setting error is registered and the SF LED lights. In this status the<br />

output values transferred from the DP master are output at the analog output modules.<br />

<strong>ET</strong> <strong>200S</strong><br />

4-26 Manual, 12/2005, A5E00514527-03