Analog electronics modules<br />

4.13 2AI I 2/4WIRE High Feature analog electronic module (6ES7134-4MB00-0AB0)<br />

2AI I 2/4WIRE High Feature Technical Specifications (6ES7134-4MB00-0AB0)<br />

Dimensions W × H × D (mm)<br />

Dimensions and Weight<br />

15 x 81 x 52<br />

(the total dimensions depend on the selected<br />

terminal module)<br />

Weight Approx. 40 g<br />

Supports isochronous operation<br />

Data for specific modules<br />

no<br />

Number of inputs<br />

Cable length<br />

2<br />

• Shielded max. 200 m<br />

Parameter length 4 bytes<br />

Voltages, currents, potentials<br />

Rated load voltage L+ (from the power<br />

module)<br />

24 VDC<br />

• Reverse polarity protection Yes<br />

Power supply of the transmitters Yes<br />

• Short-circuit protection Yes, 60 mA (for both channels)<br />

Galvanic isolation<br />

• Between the channels and backplane<br />

bus<br />

Yes<br />

• Between the channels and load voltage<br />

L+<br />

Yes<br />

• Between the channels and PE Yes<br />

• Between the channels no<br />

Permissible potential difference<br />

• Between the channels 140 VDC/100 VAC (with isolated power supply for the<br />

measuring transducer)<br />

Insulation tested<br />

Current consumption<br />

500 VDC<br />

• From load voltage L+ max. 53 mA<br />

Power dissipation of the module<br />

Diagnostics function<br />

Typically 0.85 W<br />

Status, interrupts, diagnostics<br />

• Group error Red "SF" LED<br />

• Diagnostic functions readable Yes<br />

<strong>ET</strong> <strong>200S</strong><br />

4-68 Manual, 12/2005, A5E00514527-03