New Information About the "<strong>ET</strong> <strong>200S</strong> <strong>Distributed</strong> I/O <strong>System</strong> Operating Instructions"<br />

2.2 Evaluating the Interrupts of the <strong>ET</strong> <strong>200S</strong><br />

Identification Data Access Default setting Explanation<br />

Maintenance data 1: Index 2 (Data record 232)<br />

TAG_FUNCTION Read/write (32<br />

bytes)<br />

TAG_LOCATION Read/write (22<br />

bytes)<br />

Maintenance data 2: Index 3 (data record 233)<br />

INSTALLATION_DATE Read/write (16<br />

bytes)<br />

RESERVED Read/write (38<br />

bytes)<br />

Maintenance data 3: Index 4 (data record 234)<br />

DESCRIPTOR Read/write (54<br />

bytes)<br />

- Define a unique identifier for the module in<br />

this record.<br />

- Enter the installation location of the module<br />

here.<br />

- Enter the installation date of the module<br />

here.<br />

- Reserved<br />

2.2 Evaluating the Interrupts of the <strong>ET</strong> <strong>200S</strong><br />

8.1.3 Evaluating the Interrupts of the <strong>ET</strong> <strong>200S</strong><br />

"Process interrupt lost" Diagnostics<br />

- Enter a comment on the module here.<br />

The "Process interrupt lost" diagnostics is not available for modules at present.<br />

Note<br />

Process interrupts should not be used for technological purposes (e.g. cyclical generation of<br />

process interrupts).<br />

If more than approximately 90 process interrupts are generated per second, process<br />

interrupts may be lost.<br />

<strong>ET</strong> <strong>200S</strong><br />

2-2 Product Information, 12/2006, A5E00743001-02