Digital electronic modules<br />

3.1 Parameters for digital electronic modules<br />

2DI 24 VDC<br />

High Feature<br />

4DI 24 VDC<br />

High Feature<br />

4DI 24 to 48<br />

VUC High<br />

Feature<br />

1 The input delay applies to "0" to "1" and to "1" to "0".<br />

2 Short circuit of the sensor supply.<br />

2DI/ 4DI 24 VDC<br />

Standard<br />

4DI 24 VDC/SRC<br />

Standard<br />

2DI 120 VAC<br />

Standard<br />

4DI 230 VAC<br />

Standard<br />

Range of values Default<br />

setting<br />

3 Can only be assigned parameters for the IM151-1 High Feature interface module and the IM151-7 CPU<br />

Applicability<br />

Channel 3<br />

4 If the wire break check is activated, all the unused inputs must be stabilized to prevent them from triggering a module<br />

wire break. To do this, connect a resistor between terminal 24/48 V (3, A4, 7, A8) and the free input. The resistor must<br />

provide at least 0.5 mA of input current (see "Sensor Switching" in the table of technical specifications). This ensures that<br />

sufficient current is flowing to prevent wire break detection.<br />

The sensor must supply at least 0.5 mA when switched off (otherwise wire break will be detected when switched off).<br />

Alternatively, a resistor can be connected parallel to the sensor terminals (the current must be at least 0.5 mA).<br />

3.1.2 Parameters for 4DI NAMUR<br />

Table 3-2 Parameters for 4DI NAMUR<br />

This table shows the parameters for 4DI NAMUR:<br />

4DI NAMUR Value range Default setting Applicability<br />

Diagnostic interrupt • Enable<br />

• Disable<br />

Sensor type • Channel disabled<br />

• NAMUR sensor<br />

• Open single contact<br />

• Single contact, closed<br />

with 10 kΩ<br />

• NAMUR changeover<br />

contact<br />

• Open changeover<br />

contact<br />

• Changeover contact,<br />

closed with 10 kΩ<br />

Pulse stretching • None<br />

• 0.5 s<br />

• 1 s<br />

• 2 s<br />

Diagnostics<br />

• Enable<br />

No sensor supply<br />

• Disable<br />

Disable Module<br />

Channel disabled Channel<br />

None Channel<br />

Disable Module<br />

<strong>ET</strong> <strong>200S</strong><br />

3-2 Manual, 12/2005, A5E00514527-03