New Information About the "<strong>ET</strong> <strong>200S</strong> <strong>Distributed</strong> I/O <strong>System</strong> Manual"<br />

3.4 2AI I 2/4WIRE High Feature Analog Electronic Module (6ES7134-4MB02-0AB0)<br />

2AI I 2/4WIRE High Feature Technical Specifications (6ES7134-4MB02-0AB0)<br />

Dimensions and weight<br />

Dimensions W x H x D (mm)<br />

15 x 81 x 52<br />

(the total dimensions depend on the selected<br />

terminal module)<br />

Weight Approx. 45 g<br />

Supports isochronous operation<br />

Data for specific modules<br />

* Yes<br />

Supports I&M functions Yes<br />

Number of inputs<br />

Cable length<br />

2<br />

• Shielded Max. 200 m<br />

Parameter length 12 bytes<br />

Analog value representation S5 and S7 format<br />

* Is supported if no interference frequency suppression or smoothing is configured.<br />

Voltages, currents, potentials<br />

Rated load voltage L+ (from the power module) 24 VDC<br />

• Reverse polarity protection Yes<br />

Power supply of the transmitters Yes<br />

• Short-circuit protection Yes, 60 mA (for both channels)<br />

Galvanic isolation<br />

• Between the channels and backplane bus Yes<br />

• Between the modules and load voltage L+ No at 2-wire<br />

Yes at 4-wire<br />

• Between the channels and PE Yes<br />

• Between the channels No<br />

• Permissible potential difference<br />

• Between the channels 140 VDC/100 VAC (with isolated power supply<br />

for the measuring transducer)<br />

• Insulation tested 500 VDC<br />

• Current consumption<br />

• From the load voltage L+<br />

(no sensor supply)<br />

48 mA max.<br />

• Power dissipation of the module Typically 1.2 W<br />

Status, interrupts, diagnostics<br />

Diagnostics functions<br />

• Group error Red "SF" LED<br />

• Diagnostics functions readable Yes<br />

• Process interrupts * Configurable, violation of upper and lower limits<br />

* Process interrupts are only sent if the process interrupt mechanism is not overloaded.<br />