Analog electronics modules<br />

4.6 2AI U Standard analog electronic module (6ES7134-4FB01-0AB0)<br />

Block diagram<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<strong>ET</strong> <strong>200S</strong><br />

4-40 Manual, 12/2005, A5E00514527-03<br />

<br />

Figure 4-6 Block diagram of the 2AI U Standard<br />

<br />

2AI U Standard Technical Specifications (6ES7134-4FB01-0AB0)<br />

<br />

Dimensions W × H × D (mm)<br />

Dimensions and Weight<br />

15 x 81 x 52<br />

(the total dimensions depend on the selected<br />

terminal module)<br />

Weight Approx. 40 g<br />

Supports isochronous operation<br />

Data for specific modules<br />

no<br />

Number of inputs<br />

Cable length<br />

2<br />

• Shielded max. 200 m<br />

Parameter length 4 bytes<br />

Voltages, currents, potentials<br />

Rated load voltage L+ (from the power<br />

module)<br />

24 VDC<br />

• Reverse polarity protection Yes<br />

Galvanic isolation<br />

• Between the channels and backplane bus Yes<br />

• Between the channels and load voltage L+ Yes<br />

• Between the channels no<br />

Permissible potential difference<br />

• Between the inputs and MANA (UCM) 2 VACSS<br />

• Between MANA and the central grounding<br />

point (UISO)<br />

75 VDC / 60 VAC<br />

Insulation tested<br />

Current consumption<br />

500 VDC<br />

• From load voltage L+ max. 30 mA<br />

Power dissipation of the module Typically 0.6 W<br />

Status, interrupts, diagnostics