Analog electronics modules<br />

4.5 Parameters for analog electronic modules<br />

4.5.3 Parameters for analog electronic modules 2AI U High Speed, 2AI I 2WIRE High<br />

Speed and 2AI I 4WIRE High Speed<br />

Table 4-32 Parameters for analog input modules U, I High Speed<br />

2AI U High Speed 2AI I 2WIRE High<br />

Speed<br />

2AI I 4WIRE High<br />

Speed<br />

Group diagnosis (parameter assignment error, internal • disable<br />

error)<br />

• Enable<br />

Diagnostics: Overflow/underflow • disable<br />

• Enable<br />

--- Diagnostics: Wire Diagnostics: Wire • disable<br />

break<br />

break<br />

• Enable<br />

Smoothing • None<br />

• Weak<br />

• Medium<br />

• Strong<br />

Type/range of --- --- • De-activated<br />

measurement<br />

• ± 10 V<br />

• ± 5 V<br />

• ± 2.5 V<br />

• Up to 5 V<br />

--- Type/range of --- • De-activated<br />

measurement<br />

• 4 to 20 mA<br />

• 0 to 20 mA<br />

--- --- Type/range of • De-activated<br />

measurement • 4 to 20 mA<br />

• 0 to 20 mA<br />

• ± 20 mA<br />

See also<br />

Range of values Default setting Applicability<br />

disable Module<br />

disable Module<br />

disable Channel<br />

None Channel<br />

± 10 V Channel<br />

4 to 20 mA Channel<br />

4 to 20 mA Channel<br />

Note<br />

If you deactivate a channel of the HIGH SPEED modules, you do not achieve any speed<br />

advantage on account of the measuring procedure used.<br />

Connecting Thermocouples (Page 4-19)<br />

<strong>ET</strong> <strong>200S</strong><br />

Manual, 12/2005, A5E00514527-03 4-29