SSI<br />

The transfer of path information takes place synchronously according to the SSI protocol<br />

(Synchronous Serial Interface). The SSI protocol is used with absolute position sensors.<br />

Glossary<br />

SSL (<strong>System</strong> Status List)<br />

The <strong>System</strong> Status List SSL describes the current status of the automation system: It gives<br />

an overview of the setup, the current parameter settings, the actual statuses and processes<br />

in the CPU and the assigned modules.<br />

The data of the SSL can only be read and not modified.<br />

Stationary wiring<br />

All the wiring-carrying elements (terminal modules) are mounted on a rail. The power and<br />

electronic modules are plugged onto the terminal modules.<br />

Switch<br />

SYNC<br />

PROFIBUS is a linear network. The communication nodes are connected with one another<br />

by means of a passive line - the bus.<br />

By contrast, the Industrial Ethernet consists of point-to-point connections: each<br />

communication node is directly connected to exactly one communication node.<br />

If a communication node is connected with several communication nodes, this<br />

communication node is connected to the port of an active network component - the switch.<br />

Additional communication nodes (including switches) can now be connected to the other<br />

ports of the switch. The connection between a communication node and the switch remains<br />

a point-to-point connection.<br />

A switch also has the task of regenerating and distributing received signals. The switch<br />

"learns" the Ethernet address(es) of a connected PROFIN<strong>ET</strong> device or other switches and<br />

only forwards signals, which are destined for the connected PROFIN<strong>ET</strong> device or the<br />

connected switch.<br />

A switch has a specific number of ports. You connect at most one PROFIN<strong>ET</strong> device or<br />

additional switch to each port.<br />

This is a control command of the DP master to a group of DP slaves.<br />

With the SYNC control command the DP master prompts the DP slave to freeze the statuses<br />

of the outputs at the value at that moment. With the subsequent frames, the DP slave stores<br />

the output data, but the statuses of the outputs remain unchanged.<br />

After each new SYNC control command, the DP slave sets the outputs that it has stored as<br />

output data. The outputs are not cyclically updated again until the DP master sends the<br />

UNSYNC control command.<br />

Technological modules<br />

Modules which are equipped with technological functions, e.g. counting pulses, positioning<br />

functions, control of step-action motor power sections.<br />

<strong>ET</strong> <strong>200S</strong><br />