Stand-Alone System Inverter Voltage Check<br />

For the AC appliances, the battery voltage is compared with the inverter voltage. Both<br />

components are loaded from the database and have to be checked against the system<br />

voltage.<br />

Battery Voltage Check<br />

If your system has direct battery connection, the battery voltage sets the modules’ working<br />

point. The battery voltage is dependent on the charge condition. <strong>PV*SOL</strong> ® works with a<br />

characteristic curve for the (averaged) voltage.<br />

These benchmark figures are compared with two working points for the modules’ MPP<br />

voltage, ie the MPP voltage at 500 W/m² and 25°C, and at 1000 W/m² and 25 C (STC)<br />

A message appears if the minimum battery voltage is less than 60% and the maximum<br />

battery voltage is larger than the corresponding MPP voltage.<br />

Simulation is blocked if the minimum battery voltage is less than 40% and the maximum<br />

greater than 110% of the corresponding MPP voltage.<br />

MPP Tracker Output Check<br />

If an MPP tracker is used, a check is required to see if the MPP tracker’s output<br />

corresponds to the PV output. If the figure is exceeded the PV energy produced will be<br />

reduced, if the figure is not reached the MPP tracker works at a poor efficiency rate.<br />

A message appears if the MPP tracker’s output is less than 90% and more than 120% of<br />

the PV output. MPP tracker outputs less than 33% and more than 500% of the PV output<br />

are not accepted.<br />

MPP Voltage Check<br />

The MPP tracker’s MPP tracking range is compared with the module array’s MPP voltages.<br />

The voltage decreases with increasing temperature and decreasing radiation. The<br />

definition of the working points is as described in the grid connected system check.<br />

For both of these working points the module array’s MPP voltage is calculated and<br />

compared with the MPP tracker’s MPP tracking range.<br />

A message warning of discrepancies appears if the MPP tracker’s threshold values vary by<br />

more or less than 10% from the modules. Not reaching the lower MPP threshold of around<br />

50% or exceeding the upper MPP threshold of around 25% is not permitted.<br />

Cabling checks are made on both types of systems, and on each PV array.<br />

DC Cabling Check<br />

The flow of current through the cabling under standard test conditions (STC) is defined by<br />

the module current flow under STC and the number of parallel-connected modules in an<br />

array. This should not be more than the permitted electrical capacity of the cabling.<br />