10.1.2.6 Back-up generator<br />

(stand-alone) System > Technical data > Option System with back-up generator > Back-up generator<br />

If you plan a system with a Back-up generator, a corresponding tab appears.<br />

The following data on the system are displayed in summary:<br />

PV output, gross area, active solar surface<br />

-> Requirement:<br />

On the System page, the option System with back-up generator is selected.<br />

-> How to proceed:<br />

1. Enter the Power rating.<br />

2. Enter the Minimum power output of the intended back-up generator.<br />

A back-up generator which should always meet consumption in an emergency must be able<br />

to supply the maximum power of the appliances (corrected with the battery charger<br />

efficiency). The generator modulates between the minimum and maximum power output.<br />

With a single-stage generator, the minimum power output is the same as the power rating.<br />

3. Enter the Fuel consumption. This is required to calculate pollutant emissions and<br />

for the Economic efficiency calculation.<br />

4. The Maximum power of the appliances and the Total battery capacity are<br />

displayed.<br />

Battery charger<br />

5. Enter the Efficiency of the AC/DC conversion.<br />

6. Enter the Switch on threshold (related to the nominal battery capacity), which may<br />

not be lower than the battery's discharge threshold (see page Charge controller).<br />

7. Enter the Switch off threshold (related to the nominal battery capacity) for the<br />

battery charging.<br />

8. Enter the Switching on times for battery charging.<br />

The back-up generator always ensures security of supply for the appliance and<br />

adherence to the lower battery discharge threshold. Once the back-up generator<br />

has turned on due to the battery reaching the lower discharge threshold, it only<br />

switches off on reaching the switch off threshold. A condition for this, however, is<br />

that the time switch is activated.<br />

! As meeting the requirements of the appliances takes priority, the battery also<br />

charges when the generator is supplying too much energy to meet the load on<br />

account of its minimal power output.<br />