LVDT Jumper Settings<br />
The following may be set on the signal conditioning module by means of jumpers: Buss<br />
out pin assignments, buss in pin assignments, bussed in signal sum and difference, and<br />
input amplification.<br />
Input/Output Jumpers<br />
To buss a signal from one <strong>Accusetter</strong> II to another connect an interface cable, Edmunds<br />
#4550203, from the Input/Output "A" connector on the rear of one column to the<br />
Input/Output "B" connector on the rear of the next column. Multiple columns may be<br />
connected in this way.<br />
If a signal is to be bussed out to another <strong>Accusetter</strong> II or external device the pin<br />
assignment, from 1 to 6, must be set using the jumpers as follows. Note: To avoid buss<br />
contention, assign one pin per signal. See figure 4.5.<br />
A OUT - Use this jumper to assign a pin number, 1 through 6, to buss out the signal from<br />
input A. This is a low level signal.<br />
B OUT - Use this jumper to assign a pin number, 1 through 6, to buss out the signal from<br />
input B. This is a low level signal.<br />
C I/O - Use this jumper to assign a pin number, 1 through 6, to buss out the signal from<br />
input C to another <strong>Accusetter</strong> or external device or to buss in a signal from<br />
another <strong>Accusetter</strong> to input C. This is a low level signal.<br />
D I/O - Use this jumper to assign a pin number, 1 through 6, to buss out the signal from<br />
input D to another <strong>Accusetter</strong> or external device or to buss in a signal from<br />
another <strong>Accusetter</strong> to input D. This is a low level signal.<br />
SUM HI - Use this jumper to assign a pin number, 1 through 6, to buss out the sum of<br />
all inputs included in the check designated as being "Buss Out" on the System,<br />
<strong>Co</strong>mm menu. This is a high level signal (+/-2.5V).<br />
SUM LO - Use this jumper to assign a pin number, 1 through 6, to buss out the sum of<br />
all inputs included in the check designated as being "Buss Out" on the System,<br />
<strong>Co</strong>mm menu. This is a low level signal.<br />
NOTE: Each pin can have only one input or output assigned. For example, if A OUT is<br />
assigned to pin number 6 then no other input or output can be assigned to pin number 6.<br />
NOTE: If an output is not used place the jumper on only one pin .<br />
4-7