10.07.2015 Views

PXR3 Instruction Manual - Coulton Instrumentation

PXR3 Instruction Manual - Coulton Instrumentation

PXR3 Instruction Manual - Coulton Instrumentation

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Retransmission output type setting (Setting range: 0 to 3) (Option)[Description]• This parameter is used to set the retransmission outputtype.The means of the set values are as shown below.Set value Output type0 PV1 SV2 MV3 DVRelated parameters: (page 68)(page 68)[Setting example] Changing the retransmission output type from the process value (PV) to theset value (SV)DisplayOperating procedurePV indicationPress and hold the SEL key for 5 seconds.will be displayed.Press the key to display .Press the SEL key once.The current setting (0 : PV retransmission) will be displayed.Press the or key to flicker and to display (SV retransmission).Press the SEL key once. will be displayed and 1 (SV retransmission) will be registred for theretransmission output type. After that, the controller will operate with the retransmission output being SV.SV indicationPV indication(Repeat the procedure from 3 to 5 to check the set value.)If you want to display the operation status, press and hold theThe SV will be displayed on the display area.If unoperated state continues, the PV will be displayed.SEL key for two seconds.67

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!