• The segment in which both the ramp time and soak timeare set to "0" is skipped.[Ex]SV-1: 50 SV-2:200 SV-3:100TM1r:0.10 TM2r:0.00 TM3r:1.00TM1S:0.05 TM2S:0.00 TM3S:0.7520010050PVTM1r TM1S TM3r TM3S• The SV limit function is valid even while the ramp-soakoperation is running.Although the set value (SV-n) remains unchanged, theSV under ramp-soak operation is affected by the limitfunction. Therefore, the pattern is as shown in the figureon right, and it may not change according to the originalset time.SV-1SV-2PVSV-3Pattern of the programPattern that is affectedby the SV limit functionTM1r TM1S TM2r TM2S TM3r[Setting example] Setting the 1st target SV to 400°CDisplayPV indication1.2.3.4.Press and hold the SEL key for three seconds.will be displayed.Press the key to display .Press the SEL key once.The current setting ( ) will be displayed.Operating procedurePress the keys to flicker and to display .5.Press the SEL key once. will be displayed and 400˚C will be registered for the 1st targetvalue.(Repeat the procedure from 3 to 5 to check the set value.)SV indication6.If you want to display the operation status, press and hold theThe SV will be displayed on the display area.SEL key for two seconds.PV indicationIf unoperated state continues, the PV will be displayed.48