3 Usage (Read before using)Name of Functional Parts and Functions2 1456SVC1C2AL1AL2SEL3S1 S2 S3Model : <strong>PXR3</strong>Setting keysS1NameSelect keyFunctionThe key shifting to the 1st, the 2nd or the 3rd block parameter, switching the displaybetween parameter and the data at the 1st, the 2nd and the 3rd block.S2S3Up keyDown key· The numerical value is increased by pressing the key once. The numerical valuekeeps on increasing by pressing the key continuously.· For searching parameters within the 1st, the 2nd and the 3rd block.· The numerical value is decreased by pressing the key once. The numerical valuekeeps on decreasing by pressing the key continuously.· For searching parameters within the 1st, tne 2nd and the 3rd block.Display/IndicationqwNameProcess value (PV)/Set value (SV)/parameter name or parametersetting displaySet value (SV) indication lampFunction1) Displays a process value or set value at operation mode.2) Displays the parameter name or settings at parameter settingmode.3) Displays the various error indications (refer to the “8. Errorindications”).4) Flickers at Standby mode when SV is displayed.5) Displays the set value (SV) and “SV-x” (x:1 to 4) alternatelywhen the SV-switching function is used and SV is displayed.1) The lamp is lit while a set value (SV) is displayed.2) Flickers while the process value (PV) is displayed in Standbymode.ertyAuto-tuning/self-tuning indicatorControl output indication lampAlarm output 1 (ALM1)indication lamp (Note 1)Alarm output 2 (ALM2)indication lamp (Note 1)The lamp flickers while the PID auto-tuning or the self-tuning isbeing performed.C1 : The lamp is lit while the control output 1 is ON.C2 : The lamp is lit while the control output 2 is ON. (Note 1)The lamp is lit when the alarm output 1 is activated.It flickers during ON-delay operation.The lamp is lit when the alarm output 2 is activated.It flickers during ON-delay operation.Note 1) Control output 2 and alarm function are optional.– 12 –
4 Display and operationStandby mode· To perform standby operation, set "STby" as ON in the1st block parameter.· Standby mode:SV indication lamp flickers (Output) Control outputs (1 and 2) and alarm outputs (all)are not provided. However, depending on setting of "P-n1",SVcontrol action, control outputs are provided at the abnormalShowing the C1C2processinput.AL1AL2value (PV)No alarm output is provided at standby mode, even inSEL(Fault-condition).Showing theset value(SV)SVC1C2AL1AL2Press theSELonceonceSV indication lamp is litSELThe set value (SV) flickersCaution(Control) Control is not performed.(Display) While PV being displayed ; SV indication lampflickers.While SV being displayed ; SV display value flickers.CautionBe careful since the equipment does notprovide output of the alarm of the mainunit abnormality during the standby operation.The SV display does not flicker while the 1st, 2ndand 3rd block parameters are displayed.(Setting) SV and parameter settings are able to perform.Operation modeSwitching by1st blockSTby settingsShowing theprocessvalue (PV)SVC1C2AL1AL2SEL1 Change of set value (SV)Press theSELonceonceSV indication lamp is lit2 Shift to the 1st, 2nd and 3rd block parameterTo shift to the other blocks, press theSELkey.Showing theset value(SV)SVC1C2AL1AL2CautionDepending on the pressing time ofyou can select the block to shift.SELkey,SELSEL pressing time Shifting blockThe set value (SV) canbe changed.After the data setting, the data are registeredautomatically in 3 seconds.Press the SEL for 2 sec. 1 Parameter selection3 Shift to operating conditionOperation mode(SV display)SVC1C2AL1AL2Parameter setting mode2Press theSEL once.About 1 sec pressingAbout 3 sec pressingAbout 5 sec pressingParameter settingsSVC1C2AL1AL21st block2nd block3rd blockSVC1C2AL1AL2Switching bythe SEL keySELSELSELParameter setting procedure1 Select a parameter you want toset by pressing the orkey.2-1 SELPress the key to displaythe parameter set value.2-2 Pressing the or key,change the parameter setvalue.2-3 After the parameter has beenchanged, press the SEL keyfor registration.3 To shift to Operation/Standbymode, press the SEL key for 2 sec.Parameter search.Press the . Press the .SVC1C2AL1AL2SELPress theSEL once.SELSVC1C2AL1AL2Parameter set value change.SELIncreases parameterset valueDecreases parameterset valueRegisters parameter set value, and returnsto the parameter selection mode 1 .When the set value ischanged, the numeric valueflickers.CautionIf it is left in this state for 30seconds, the change becomesinvalid, and it returns toOperation/Standby mode.By repeating the same procedure, the parameters can be displayedaccording to the parameter list shown in “5, Setting methods of4 If unoperated state continues for30 seconds, it returns to Operation/Standby mode.CautionAfter the parameter has been changed,if unoperated state continues for 30 seconds without pressing thesetting change becomes invalid.SELkey,– 13 –