e Third block parametersSpecifying control system and action, and output direction at input burn-out(Setting range: 0 to 19)[Description]• This parameter specifies action (Single/Dual and Heating/Cooling), and output direction at input burn-out.• The standard model (single output) or the heating/coolingcontrol output (dual output) are available.• There is defference of hardware between the standardmodel and the heating/cooling control output model. Setthe code that is applicable to your controller.• In general, reverse action is applyed for the heatingprocess and direct action is applyed for the coolingprocess.* The lower limit of a burn-out output indicatesthat output is set to OFF, or 4mA or less. Theupper limit indicates that output is set to ON,or 20mA or more.* Retransmission output is kept operated. However,if the type of retransmission output is setto the MV, the output becomes the same as theoutput at burnout.• Control operation code tableCodeModel(P-n1)01Standard2(single)34567891011 Heating12 /Cooling13 (dual)141516171819Control actionOutput 1ReverseDirectReverseDirectReverseDirectOutput 2...DirectReverseBurn-out output*Output 1 Output 2Lower limitUpper limit...Lower limitUpper limitLower limitLower limitUpper limitLower limitUpper limitUpper limitLower limitLower limitUpper limitLower limitUpper limitUpper limitLower limitLower limitUpper limitLower limitUpper limitUpper limitLower limitLower limitUpper limitLower limitUpper limitUpper limit[Setting example] Changing the "Reverse/Lower limit for burn-out output" to the "Direct/Upper limit for burn-out output"DisplayPV indicationSV indicationPV indication1.2.3.4.5.Press and hold the SEL key for five seconds.will be displayed.Press the SEL key once.The current setting ( ) will be displayed.Operating procedurePress the or keys to flicker and to display .Press the SEL key once. will be displayed and will be registered for . After that,the controller will operate with the "Direct/Upper limit for burn-out output" selected.(Repeat the procedure from 2 to 4 to check the set value.)If you want to display the operation status, press and hold the SEL key for two seconds.The SV will be displayed on the display area.If unoperated state continues, the PV will be displayed.49

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!