HYS (Hysteresis) mode at ON/OFF control (Settings: oFF/on)[Description]• This parameter is used for selecting the hysteresis operationmode at ON/OFF control.onoF : OFFonoF : ON: Starts the ON/OFF control at the values ofHYS HYSSV+ and SV- .22: Starts the ON/OFF control at the values ofSV and SV+HYS, or SV and SV-HYS.• Related parameters: (page 20)(page 23)(page 49)Reverse actionDirect actionHYSSVHYSSVHYSSVHYSSV[Setting example] Setting the hysteresis mode to ONDisplayOperating procedurePV indication1.2.3.4.Press and hold the SEL key for three seconds.will be displayed.Press the key to display .Press the SEL key once.The current setting ( ) will be displayed.Press the key to flicker and to display .SV indicationPV indication5.6.Press the SEL key once. will be displayed and the hysteresis action ON will be registeredfor . After that, the controller will operate with the hysteresis being as shown in the figureof ON above.(Repeat the procedure from 3 to 5 to check the set value.)If you want to display the operation status, press and hold theThe SV will be displayed on the display area.If unoperated state continues, the PV will be displayed.SEL key for two seconds.32