, Hysteresis of alarm 1 and 2 (Setting range: 0 to 50% FS) (Option)[Description]• The alarm is detected in the two-position operation (ON/OFF). The hysteresis means the difference between theinput at ON and the input at OFF. For example, the hysteresisof 5°C means that the range between ON and OFFis 5°C.• Setting the decimal place with allows decimal pointto be placed automatically.• Hysteresis can be set for each alarm.A1hy• ALM1AL1• Upper limit alarm5˚CON• ALM2A2hyOFFAHInputAL2• Lower limit alarmON5˚COFFALInput• Range alarm5˚CON5˚COFFOFFALAH[Setting example] Changing the hysteresis of alarm 2 from 1°C to 3°CDisplayPV indicationSV indicationPV indication1.2.3.4.5.6.Press and hold the SEL key for five seconds.will be displayed.Press the key to display .Press the SEL key once.The current setting ( ) will be displayed.Operating procedurePress the or keys to flicker and to display .Press the SEL key once. will be displayed and 3˚C will be registered for . Afterthat, the controller will operate with the hysteresis of alarm 2 being 3˚C.(Repeat the procedure from 3 to 5 to check the set value.)If you want to display the operation status, press and hold the SEL key for two seconds.The SV will be displayed on the display area.If unoperated state continues, the PV will be displayed.53