PC3000 Complete Installation guide iss 12 - Elektro-Trading
PC3000 Complete Installation guide iss 12 - Elektro-Trading
PC3000 Complete Installation guide iss 12 - Elektro-Trading
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
4 Channel Analogue Input Module<br />
9-16<br />
(5) Change the parameter Cal_Mode from Run ( 0) to CJC (4) in order to commence<br />
calibration. The mode will revert back to Run ( 0) on completion of calibration.<br />
(6) The value read by the CJC_Val will be the temperatue of the CJC sensor i.e.<br />
approximately the temperature of the module.<br />
(7) Change the parameter Cal_Mode from Run ( 0) to Save ( 1) in order to store the<br />
new calibration data. On completion of the save operation the Cal_Mode will<br />
automatically revert to Run ( 0) and Status_Info will indicate Ok ( 1)<br />
(8) In the event of an error occurring whilst calibrating e.g.entering the wrong value<br />
for the applied millivolt input, the calibration procedure may be aborted by<br />
changing Input_Type to a different range and then back to its’ original value. The<br />
calibration data that existed prior to the session will be restored.<br />
Calibration of high level inputs<br />
This applies to module variant:<br />
<strong>PC3000</strong>/AI/VERSION3/V4<br />
There are four ranges to be calibrated; 1V, 2V, 5V, and 10V. Each range is calibrated<br />
in a similar fashion. Ranges are bi-polar i.e. -1V to 1V etc.The parameter Input_Type<br />
must be set to the appropriate range prior to calibration.The millivolt reference<br />
source should be connected to the input module as detailed.<br />
Zero<br />
+<br />
-<br />
<strong>12</strong>v 9.999v 0v + mV -<br />
EUROTHERM 239<br />
xxx<br />
xxxxxxxxx<br />
xxxxxxxxx<br />
xxxxxxx<br />
xxxxxxx<br />
xxxxxxx<br />
The calibration input voltages are arbitrary but the following points are suggested for<br />
each of the ranges:<br />
Input Range Low cal point High cal point<br />
1V -0.9V 0.9V<br />
2V -1.8V 1.8V<br />
5V -4.5V 4.5V<br />
10V -9.0V 9.0V<br />
nc<br />
Function<br />
V+<br />
V-<br />
CH1 CH2<br />
2 5<br />
3<br />
4<br />
Terminal Number<br />
6<br />
7<br />
CH3 CH4<br />
9 <strong>12</strong><br />
10<br />
11<br />
13<br />
14<br />
<strong>PC3000</strong> <strong>Installation</strong>