Local Controller Plus Module<br />
6-2<br />
Type Code<br />
Local Controller Module <strong>PC3000</strong>/LCM-PLUS/VERSION3/NOMEM/NOMEM/3<strong>12</strong><br />
Plus fitted with 5<strong>12</strong>K of<br />
RAM.<br />
Local Controller Module <strong>PC3000</strong>/LCM-PLUS/VERSION3/5<strong>12</strong>KRAM/5<strong>12</strong>KRAM/3<strong>12</strong><br />
Plus fitted with 1536K of<br />
RAM.<br />
Local Controller Module <strong>PC3000</strong>/LCM-PLUS/VERSION3/NOMEM/<strong>12</strong>8KRAM/3<strong>12</strong><br />
Plus fitted with 5<strong>12</strong>K<br />
plus <strong>12</strong>8K for storage<br />
of source program<br />
Connections to serial ports<br />
All serial communication connections including the extension rack interface are<br />
made via high density, latching, shielded connectors.<br />
LCM serial ports A, B or C and extension<br />
rack connector<br />
Pin Number RS232<br />
Operating Mode<br />
RS485 RS485<br />
2-wire 4-wire<br />
1 Rx N/A N/A<br />
2 Tx N/A N/A<br />
3 N/A Rx/Tx- Tx-<br />
4 N/A Rx/Tx+ Tx+<br />
5 N/A N/A Rx-<br />
6 N/A N/A Rx+<br />
7 0V 0V 0V<br />
8 0V 0V 0V<br />
Cable screen Rack earth Rack earth Rack earth<br />
8<br />
7<br />
6<br />
5<br />
Notes<br />
1. The RS232 connections on the<br />
LCM-Plus differ from those on the version 2 ICMs.<br />
2. RS232 is not available on Port C, as there are no connections to Port C's pins 1 and 2.<br />
3. The connection system automatically connects the cable screen to the LCM's case, and<br />
hence to the rack.<br />
4. In 4-wire RS485 mode the receive pair may be exchanged with the transmit pair on<br />
Port A using links on the PCB.<br />
A range of cable assemblies is available from Eurotherm Controls to allow direct connection<br />
to a variety of standard devices. A list of available cable types may be found in the <strong>PC3000</strong><br />
Technical Summary (HA022230)<br />