Local Controller Plus Module<br />

6-2<br />

Type Code<br />

Local Controller Module <strong>PC3000</strong>/LCM-PLUS/VERSION3/NOMEM/NOMEM/3<strong>12</strong><br />

Plus fitted with 5<strong>12</strong>K of<br />

RAM.<br />

Local Controller Module <strong>PC3000</strong>/LCM-PLUS/VERSION3/5<strong>12</strong>KRAM/5<strong>12</strong>KRAM/3<strong>12</strong><br />

Plus fitted with 1536K of<br />

RAM.<br />

Local Controller Module <strong>PC3000</strong>/LCM-PLUS/VERSION3/NOMEM/<strong>12</strong>8KRAM/3<strong>12</strong><br />

Plus fitted with 5<strong>12</strong>K<br />

plus <strong>12</strong>8K for storage<br />

of source program<br />

Connections to serial ports<br />

All serial communication connections including the extension rack interface are<br />

made via high density, latching, shielded connectors.<br />

LCM serial ports A, B or C and extension<br />

rack connector<br />

Pin Number RS232<br />

Operating Mode<br />

RS485 RS485<br />

2-wire 4-wire<br />

1 Rx N/A N/A<br />

2 Tx N/A N/A<br />

3 N/A Rx/Tx- Tx-<br />

4 N/A Rx/Tx+ Tx+<br />

5 N/A N/A Rx-<br />

6 N/A N/A Rx+<br />

7 0V 0V 0V<br />

8 0V 0V 0V<br />

Cable screen Rack earth Rack earth Rack earth<br />

8<br />

7<br />

6<br />

5<br />

Notes<br />

1. The RS232 connections on the<br />

LCM-Plus differ from those on the version 2 ICMs.<br />

2. RS232 is not available on Port C, as there are no connections to Port C's pins 1 and 2.<br />

3. The connection system automatically connects the cable screen to the LCM's case, and<br />

hence to the rack.<br />

4. In 4-wire RS485 mode the receive pair may be exchanged with the transmit pair on<br />

Port A using links on the PCB.<br />

A range of cable assemblies is available from Eurotherm Controls to allow direct connection<br />

to a variety of standard devices. A list of available cable types may be found in the <strong>PC3000</strong><br />

Technical Summary (HA022230)<br />

4<br />

3<br />

2<br />

1<br />

A<br />

B<br />

C<br />

EXT<br />

RACK<br />

<strong>PC3000</strong> - <strong>Installation</strong> Guide