Types of communication<br />

<strong>PC3000</strong> - <strong>Installation</strong> Guide<br />

Local Controller Plus Module<br />

Point-to-point communications<br />

RS232 can only be used for point-to-point communications such as the programming<br />

tools communicating with one LCM-Plus. RS485 may also be used for this type of<br />

communication where an increased level of noise immunity and connection distance<br />

is required.<br />

Note: The RS232<br />

Tx<br />

RS232<br />

Tx<br />

connections on the LCM-<br />

Plus differ from those on<br />

Rx Rx<br />

the version 2 ICM.<br />

Version 3 ICM will work<br />

PS<br />

<strong>PC3000</strong> with either cable.<br />

All communication channels have functional insulation (50V) from the system, but<br />

share a common ground - 0V. Care is therefore required when mixing RS232 and<br />

RS485 communications which may well require insulation between them.<br />

Multi-drop communications<br />

In multi-drop communications one master is connected to many slaves. Multi-drop<br />

communications requires the ports to be RS485.<br />

Master<br />

<strong>PC3000</strong><br />

Tx+<br />

Tx-<br />

4-wire RS485<br />

Rx+ Rx+<br />

Rx-<br />

Termination<br />

Resistor<br />

Termination<br />

Resistor<br />

Tx+<br />

Tx-<br />

Rx-<br />

Tx+<br />

Tx-<br />

Rx+<br />

Rx-<br />

Tx+<br />

Tx-<br />

Rx+<br />

Rx-<br />

Slave<br />

<strong>PC3000</strong><br />

Slave<br />

900EPC<br />

Slave<br />

584/590 Drive<br />

6-5