Profibus Master Fieldbus Card<br />

Module identification<br />

19-2<br />

Module may be identified by means of a label visible through the top of the<br />

detachable fascia carrying the text COM.<br />

Additionally, a label fitted to the side of the module carries details of the serial<br />

number etc. The product code is included and should read:-<br />

<strong>PC3000</strong>/COMM/VERSION3/PROFIDP/MASTER<br />

The COM-DPM card is the 2K varient, which describes the size of the dual port<br />

RAM.<br />

Connections<br />

User connection to the module is via two 9 way, D-type connectors at the front of the<br />

module.<br />

Configuration port<br />

The top connector is a male and is an unisolated RS232 configuration port. It is for<br />

connection to a computer running the configuration software for download and<br />

diagnostics.<br />

Pin No. Function<br />

2<br />

3<br />

5<br />

Tx<br />

Rx<br />

Common<br />

Table 1 Configuration port connections<br />

Profibus port<br />

The bottom connector is a female and is the isolated RS485 Profibus port. The actual<br />

network connection to remote instruments via a twisted pair cable and the D-type<br />

connector header should contain a terminator network as shown in the diagram.<br />

Pin No. Function<br />

6<br />

3<br />

8<br />

5<br />

5V<br />

Rx/Tx +ve<br />

Rx/Tx -ve<br />

0V<br />

6<br />

3<br />

8<br />

5<br />

390R<br />

220R<br />

390R<br />

Table 2 Profibus port connections<br />

Rx/Tx +ve<br />

Rx/Tx -ve<br />