4 Channel Analogue Input Module<br />
Calibration of resistance inputs<br />
9-18<br />
This applies to module variant:<br />
<strong>PC3000</strong>/AI/VERSION3/RT4<br />
This module use the Function Block, Analog_In_R. The block provides the following<br />
parameters:<br />
Input_Type 50_Ohm (0) ; 0 to 50 Ohm (-10 to 10mV)<br />
100_Ohm (1) ; 0 to 100 Ohm (-10 to 20mV)<br />
250_Ohm (2) ; 0 to 250 Ohm (-10 to 50mV)<br />
500_Ohm (3) ; 0 to 500 Ohm (-10 to 100mV)<br />
Lin_Type Lin_mV (0) ; Linear mV ranges as above<br />
Lin_Ohm (1) ; Linear Ohm ranges as above<br />
Pt_100 (2) ; Platinum resistance therm.<br />
Cal_Mode Run (0) ; Normal mode<br />
Save (1) ; Save calibration data<br />
mV_Hi (2) ; Calibrate mV (high point)<br />
mV_Lo (3) ; Calibrate mV (Low point)<br />
Res (4) ; Single point resistance cal.<br />
Cal_Hi_Pt fixed units of mV Cal point data entry<br />
Cal_Lo_Pt fixed units of mV Cal point data entry<br />
Cal_Res_P fixed units of Ohm Cal point data entry<br />
C_Cal_Hi_P fixed units of mV Stored cal data<br />
C_Cal_Lo_P fixed units of mV Stored cal data<br />
C_Cal_Res_P fixed units of Ohm Stored cal data<br />
Lead_Val fixed units of mV Diagnostic used during calibration.<br />
Voltage across lead.<br />
All other parameters identical to the Analog_In Function Block template.<br />
The calibration process has two stages:<br />
(1) Millivolt calibration<br />
(2) Resistance calibration<br />
During millivolt calibration, the sense lead input 1 ,2 , etc. must be connected to the<br />
L L<br />
respective positive input 1+, 2+ etc. by a short external wire link.<br />
Remove the links fitted to the pcb, LK101, LK201, LK301, LK401 (only 4 links on<br />
board) prior to millivolt calibration. (Prevents offset caused by sensor bias current<br />
through input filter). Access to the links requires that the plastic pcb covers are<br />
removed. Observe Static Handling procedures.<br />
There are four ranges to be calibrated; 50 ohm, 100 ohm, 250 ohm and 500 ohm.<br />
Each range is calibrated in a similar fashion.<br />
The parameter Input_Type must be set to the appropriate range prior to calibration.<br />
<strong>PC3000</strong> <strong>Installation</strong>