4 Channel Analogue Output Module<br />

10-6<br />

As an example, say that it is required to recalibrate an output at 9.5V (95% on 10V<br />

range). The parameter Hw_Cal_Hi_P will already contain the value, 95. If this value<br />

is re-entered calibration will not occur. The value must be changed to say 95.1 and<br />

then changed back to 95 in order for the data to be transmitted to the module. All<br />

calibration data must be treated accordingly.<br />

Step-by-step calibration <strong>guide</strong><br />

The actions which should be performed for calibration are described. They are<br />

described in terms of the Function Block parameters associated with calibration and<br />

are intended to be independent of the Programming Station used to perform the<br />

calibration.<br />

Outputs are calibrated on the full scale ranges (-10V to +10V and -20mA to +20mA)<br />

only.<br />

The following calibration values are recommended:<br />

Output range Low point High point<br />

-10V to +10V -90% (-9V) 90% (9V)<br />

-20mA to +20mA -90% (-18mA) 90% (18mA)<br />

(1) Select Output_type for the current or voltage mode to be calibrated.<br />

(2) Change the parameter Cal_Mode from Run ( 0) to HCal_Lo ( 4).<br />

(3) Select Hw_Cal_Lo_P, and enter a value at or near zero corresponding to the<br />

percentage of full scale required for the low calibration point e.g. -90%. The<br />

module will output its value corresponding to the percentage entered as the<br />

Hw_Cal_Lo_P<br />

(4) Read the value displayed by the DVM and record this value. As an<br />

example, assume the meter reads -8.97 at the calibration point -90%.<br />

Convert this to the percentage of full scale, in this case, -89.7%. Enter this<br />

as the value of the Hw_Cal_V. The voltage read on the meter will now<br />

equal the requested value e.g. -9.0V.<br />

(5) Change the parameter Cal_Mode from Run to HCal_Hi (5).<br />

(6) Select Hw_Cal_Hi_P, and enter a value at or near full scale corresponding to<br />

the percentage of full scale required for the high calibration point e.g. 90%. The<br />

module will output its value corresponding to the percentage entered as the<br />

Hw_Cal_Hi_P<br />

(7) Read the value displayed by the DVM and record this value. As an example,<br />

assume the meter reads 9.03 at the calibration point 90%. Convert this to the<br />

percentage of full scale, in this case, 90.3%. Enter this as the value of the<br />

Hw_Cal_V. The voltage read on the meter will now equal the requested value<br />

e.g. 9.0V.<br />

<strong>PC3000</strong> - <strong>Installation</strong> Guide