Intelligent Communications Module<br />

18-6<br />

It is not possible to cover all possible uses of the communication links to and from an<br />

ICM but the following table shows how the links would be set for some of the typical<br />

uses. In the table link LK*1 refers to LKA1 for channel A, LKB1 for channel B and<br />

LKC1 for channel C etc.<br />

Requirement Links Comments<br />

RS232 not applicable The links are ignored<br />

Point to point for RS232 connection (Port D only)<br />

RS485 LK*1 forward position Receiver terminated<br />

Point to point LK*2 forward position Tx and Rx permanently enabled<br />

4-Wire LK*3 & 4 not fitted Tx and Rx separate<br />

LKA5-8 as required Optional swap if not<br />

(port A only) in cable (Note 1)<br />

RS485 LK*1 forward position Receiver terminated<br />

Point to point LK*2 rear position Tx disabled when not transmitting,<br />

2-wire Rx disabled when transmitting<br />

(Suitable for half LK*3 & 4 fitted Tx and Rx shorted<br />

duplex protocols only) LKA5-8 horizontal<br />

(port A only)<br />

Swap not required<br />

RS485 LK*1 as required Optional receiver termination (Note 2)<br />

Master LK*2 forward position Tx and Rx permanently enabled<br />

4-wire LK*3 & 4 not fitted Tx and Rx separate<br />

LKA5-8 vertical<br />

(port A only)<br />

Swapped (Note 1)<br />

RS485 LK*1 as required Optional receiver termination (Note 2)<br />

Master LK*2 rear position Tx disabled when not transmitting,<br />

2-wire Rx disabled when transmitting<br />

(Suitable for half LK*3 & 4 fitted Tx and Rx shorted<br />

duplex protocols LKA5-8 horizontal Swap not required<br />

only) (port A only)<br />

RS485 LK*1 as required Optional receiver termination (Note 2)<br />

Slave LK*2 not fitted Tx disable when not transmitting,<br />

4-wire Rx permanently enabled<br />

LK*3 & 4 not fitted Tx and Rx separate<br />

LKA5-8 horizontal<br />

(port A only)<br />

Not swapped<br />

RS485 LK*1 as required Optional receiver termination (Note 2)<br />

Slave LK*2 rear position Tx disabled when not transmitting,<br />

2-wire Rx disabled when transmitting<br />

(Suitable for half LK*3 & 4 fitted Tx and Rx shorted<br />

duplex protocols only) LKA5-8 horizontal<br />

(port A only)<br />

Swap not required<br />