<strong>PC3000</strong> - <strong>Installation</strong> Guide<br />

The Racking System<br />

Caution<br />

Special care should be taken when removing or fitting connectors to<br />

Analogue Input modules. These modules have temperature sensors<br />

which are located at the edge of the modules’ circuit board. Always<br />

ensure that the connector is aligned correctly and is parallel to the<br />

circuit board before pushing fully home. Failure to observe caution<br />

could result in damage to the temperature sensors.<br />

Cable<br />

Wiring to the <strong>PC3000</strong> is by means of captive screws within the detachable connector<br />

and module fascia. The wiring capacity is:<br />

1 x 2.0mm2 (14 awg)<br />

or2 x 1.3mm2 (16 awg)<br />

Minimum cable size is 0.2mm2 (24 awg). The recommended conductor size is 1mm2 .<br />

All wiring may be fixed (strain-relieved) to the connector/fascia assembly by the<br />

cable tie fixing points provided.<br />

Rack earthing<br />

Caution<br />

Excessive force to clamp wires is not necessary. Maximum torque is<br />

0.4Nm.<br />

Left hand side<br />

of rack<br />

Cubicle or panel<br />

safety earth point<br />

Power supply<br />

earthed to same<br />

point<br />

3-7