<strong>PC3000</strong> - <strong>Installation</strong> Guide <strong>iss</strong>. 5<br />

4 Channel Analogue Output Module<br />

(6) Enter the required output value for a requested output of Tr_Cal_Hi_P. As the<br />

example given earlier, if it is required that the output is trimmed to produce<br />

100.2% at full scale, enter 100.2 via the parameter, Tr_Cal_Hi_V. The analogue<br />

ouput will take on this value.<br />

(7) Change the parameter Cal_Mode from TCal_Hi to Run in order to store the new<br />

calibration data.<br />

(8) In the event of an error occuring whilst calibrating e.g.entering the wrong value<br />

for the desired output level, simply re-enter the value via Tr_Cal_Hi_V or<br />

Tr_Cal_Lo_V.<br />

10-9