Rear/bulkhead mounting<br />

The rear/bulkhead mounting rack's product code is:<br />

Type Code<br />

Primary rack Note (1)<br />

<strong>PC3000</strong>/RACK/VERSION3/MAIN/REAR<br />

Extension rack Note (1)<br />

<strong>PC3000</strong>/RACK/VERSION3/EXT/REAR<br />

Note (1) For this version two types are the same.<br />

<strong>PC3000</strong> - <strong>Installation</strong> Guide<br />

The Racking System<br />

The M5 ‘A’ fixing centres are recommended for use in bulkhead (rear) mounting<br />

applications in order to distribute the cantilever load over a wider area. They may<br />

also be used in conjunction with the ‘B’ fixings to provide additional security.<br />

The diagram below shows the ‘footprint’ of the rack on its’ mounting surface. The<br />

rack backplane is covered by a metal shield and the brackets provide adequate<br />

clearance.<br />

Use 'A'. M5 fixing centres<br />

or alternative 'B' fixing<br />

centres<br />

A<br />

B<br />

135 57.15<br />

482.6<br />

465.<strong>12</strong><br />

Minimum clearance required in front of bulkhead is 330mm.<br />

It is recommended that screws penetrate the nut or other threaded medium by at least<br />

one diameter (i.e 5 or 6mm)<br />

Extension racks and multi-rack systems<br />

A multi-rack system comprises one main rack<br />

plus 1 to 7 extension racks.<br />

In order for the <strong>PC3000</strong> racks to operate<br />

without risk of over-heating, it is<br />

recommended that racks, when stacked<br />

vertically, be positioned at least<br />

3U (133mm) apart.<br />

When mounted adjacent to one another,<br />

no spacing is required. It is also recommended<br />

that the cabinet is vented and force cooled.<br />

EUROTHERM CONTROLS<br />

First rack<br />

B<br />

A<br />

<strong>PC3000</strong><br />

A 6<br />

B<br />

<strong>12</strong>2.5<br />

B<br />

A<br />

EUROTHERM CONTROLS<br />

3U (133.35mm) Min.<br />