Version compatibility<br />
<strong>PC3000</strong> - <strong>Installation</strong> Guide <strong>iss</strong>. 4<br />
Pulse Input Module<br />
This module is Version 3 and introduces a new style connector header.<br />
Version 3 modules may be used in the old Version 2 or Version 1 rack together with<br />
the enclosed new connector header.<br />
Description<br />
This module provides 2 channels for general purpose high speed counting and<br />
totalising applications, and a supply for powering encoders.<br />
A variant of this module permits decoding of quadrature encoders.<br />
The module can handle pulse inputs up to 200kHz.<br />
All data in this chapter refers to the later 'Mk 2' pulse input module.<br />
The inputs have reinforced insulation to the "System" and other modules.<br />
There is no inter-channel isolation.<br />
Caution live sensors<br />
Where one channel may be live, the installer must ensure that the other channel in the<br />
same module, is not accessible to service personnel while it is live. The installer must<br />
also ensure that this situation will not damage other connected equipment. All cables,<br />
connectors and switches for connecting external equipment to an I/O point that may<br />
be at live potential, must be mains rated.<br />
Cleaning<br />
Isopropyl alcohol may be used to clean the labels, do not use water or water based<br />
products or they will become illegible.<br />
A mild soap solution may be used to clean the exterior surfaces of this product.<br />
Module identification<br />
A label fitted to the side of the module carries details of serial number etc. Product<br />
identification is:<br />
<strong>PC3000</strong>/PI/Version2/5P2 2 channels, 5Volt input, up counter<br />
<strong>PC3000</strong>/PI/Version2/<strong>12</strong>P2 2 channels, <strong>12</strong>Volt input, up counter<br />
<strong>PC3000</strong>/PI/Version2/5Q2 2 channels, 5Volt input, quadrature counter<br />
<strong>PC3000</strong>/PI/Version2/<strong>12</strong>Q2 2 channels, <strong>12</strong>Volt input, quadrature counter<br />
Note: Different module firmware is required for modules type P and Q.<br />
Please consult your local Eurotherm office for further information.<br />
15-1