4 Channel Analogue Input Module<br />
9-2<br />
The resistance input variant may be used with two or three wire transducers.<br />
Automatic compensation for lead resistance is provided when used with three wire<br />
sources.<br />
The process level input variant permits direct connection of high level (up to 10v)<br />
signals, without the need for external attenuation.<br />
Current inputs are handled by means of an external burden resistor fitted to the<br />
detachable connector assembly. A 5 ohm burden permits the 50mV linear range to<br />
represent 10mA full scale. For 20mA inputs the range should be set to 100mV.<br />
The .../mV3/HiZ1 variant is hardware configured to give one channel of high input<br />
impedance for high level (up to 10V) and three standard mV/thermocouple inputs.<br />
The ...V2/FV2 variant is hardware configured to give two channels of frequency<br />
measurement for tachogenerators or low speed encoders, and two channels of high<br />
level (up to 10V) signal measurement.<br />
All channel configurations are user configurable via the supporting Function Block<br />
and the PC based Programming Station.<br />
All modules offer four ranges. Range selection is made via the supporting Function<br />
Block and the PC based Programming Station. Refer to the '<strong>PC3000</strong> Function Block<br />
Manual' for further details.<br />
Module identification<br />
Module may be identified by means of a label visible through the top of the detachable<br />
fascia carrying the text AI 4.<br />
Additionally, a label fitted to the side of the module carries details of serial number<br />
etc. The modules product code is included and should read:<br />
<strong>PC3000</strong>/AI/VERSION3/mV4 for millivolt inputs<br />
<strong>PC3000</strong>/AI/VERSION3/mA4 for current inputs (includes burdens)<br />
<strong>PC3000</strong>/AI/VERSION3/V4 for process level inputs<br />
<strong>PC3000</strong>/AI/VERSION3/RT4 for resistance thermometers<br />
<strong>PC3000</strong>/AI/VERSION3/mV3/HiZ1 for Zirconia probes<br />
<strong>PC3000</strong>/AI/VERSION3/V2/FV2 for frequency inputs (0-10kHz)<br />
<strong>PC3000</strong> - <strong>Installation</strong> Guide