<strong>PC3000</strong> - <strong>Installation</strong> Guide <strong>iss</strong>. 5<br />

4 Channel Analogue Output Module<br />

(8) Change the parameter Cal_Mode from HCal_Hi to (Save) in order to store<br />

the new calibration data. On completion of the save operation the Cal_Mode will<br />

automatically revert to Run and Status_Info will indicate Ok.<br />

(9) In the event of an error occurring whilst calibrating e.g.entering the wrong value<br />

for the measured voltage, the calibration procedure may be aborted by changing<br />

Cal_Mode from HCal_Hi or HCal_Lo to Run. The calibration data that existed<br />

prior to the session will be restored.<br />

The examples given assume that the channel being calibrated is in voltage mode.<br />

Current channels may be calibrated in a similar fashion. As an example say a 0 to<br />

20mA output channel produces 3mA in response to a request for 10% (2mA). A<br />

reading of 3mA corresponds to 15% and this value should be entered into the<br />

parameter Hw_Cal_V. (Tip: halve the value read from the meter and multiply by 10<br />

to get percentage of full scale)<br />

This procedure must be repeated for each channel. Note that there only need be one<br />

calibration in voltage mode, and one in current mode, as the alternative ranges are<br />

subsets and use the same calibration values.<br />

Calibration dates on the Analog Out function block<br />

The Analog_Out function block provides a calibration date:<br />

Hw_Cal_Date<br />

This represents the date of last hardware calibration for the currently selected<br />

configuration (Voltage or Current)<br />

Note: From Fb V3.00 words calibration dates are not supported.<br />

There is no method for entering a date into the parameters. Future<br />

releases will provide a facility to permit this. Calibration dates on<br />

older versions should be ignored.<br />

Other parameters associated with calibration<br />

The Analog_Out function block provides two calibration point ‘outputs’:<br />

C_Hw_Cal_Hi<br />

C_Hw_Cal_Lo<br />

This is the data read from the module at initialization and represents the value of the<br />

calibration points used on the last calibration of the currently selected range.<br />

Transducer calibration<br />

Transducer calibration provides a method of scaling and offsetting non-standard<br />

output ranges. It also provides a means for correcting actuator errors e.g. 100% or<br />

10V output does not correspond to valve fully open due to valve inaccuracy.<br />

The PC 3000 analog output module uses a two point transducer calibration scheme in<br />

10-7