Relay Output Module<br />
Connections<br />
Location<br />
16-2<br />
Connection by means of a detachable 15 way connector and fascia assembly.<br />
The following terminal assignment applies:<br />
Specification<br />
Reinforced<br />
Insulation<br />
S<br />
Y<br />
S<br />
T<br />
E<br />
M<br />
Label Function<br />
1 Output 1<br />
2 Output 2<br />
3 Output 3<br />
4 Output 4<br />
C 1 Common 1-4<br />
5 Output 5<br />
6 Output 6<br />
7 Output 7<br />
8 Output 8<br />
C 2 Common 5-8<br />
9 Output 9<br />
10 Output 10<br />
11 Output 11<br />
<strong>12</strong> Output <strong>12</strong><br />
C 3 Common 9-<strong>12</strong><br />
Termina Terminal<br />
l<br />
Note: Output <strong>12</strong> becomes System Watchdog on ../RLYFS11<br />
PSU LCM<br />
or<br />
RIM<br />
1<br />
2<br />
3<br />
4<br />
5<br />
Channels: <strong>12</strong><br />
Contact life: > 500K operations at 1 amp resistive load<br />
Mechanical life > 50M operations<br />
Max Voltage: 264V ac 50/60Hz<br />
Max Current: 1A per channel<br />
Protection: Contacts protected by RC network<br />
(Off leakage current = 2mA @ 264V ac)<br />
Insulation: Insulated as 3 groups - Ch1-4, 5-8, 9-<strong>12</strong><br />
Functional insulation Channel group to Channel group.<br />
Reinforced insulation Module to Module.<br />
6<br />
7<br />
8<br />
9<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
9<br />
10<br />
11<br />
<strong>12</strong><br />
13<br />
14<br />
15<br />
10 11 <strong>12</strong><br />
Permitted positions for this module<br />
Functional<br />
Insulation<br />
Functional<br />
Insulation<br />
<strong>PC3000</strong> - <strong>Installation</strong> Guide