4 Channel Analogue Input Module<br />
Zirconia probe input<br />
9-6<br />
The ../mV3/HiZ1 variant allows direct connection of a high impedance source such<br />
as an oxygen probe channel 1 should be set on the 2V range (Range_2). All other<br />
inputs are millivolt level.<br />
Frequency inputs<br />
The ../V2/FV2 variant supports frequncy inputs in the range 0-10kHz. Typical<br />
sources include tachogenerators and low speed encoders. Channels 1 and 3 support<br />
frequency inputs. All other channels are process level voltage inputs.<br />
nc<br />
Function<br />
F+<br />
NC<br />
F-<br />
Filter earth connections and signal screens<br />
Each channel is fitted with an LC input filter to provide rejection of high frequency<br />
noise spikes on the input signal. The return for this filter is connected to earth by<br />
means of a spring clip fitted to the rack pcb <strong>guide</strong> and the rack earth connection.<br />
nc<br />
nc<br />
Function<br />
HiZ+<br />
NC<br />
HiZ-<br />
Function<br />
TC+<br />
CJSensor<br />
TC-<br />
CH1<br />
CH3, 4 connections as standard<br />
CH1<br />
2<br />
NC<br />
4<br />
2<br />
3<br />
4<br />
CH3<br />
9<br />
NC<br />
Note: CH 2 and 4 connections as standard voltage inputs<br />
Notes<br />
1. Frequency scaling of frequency input is 1V ≡1k Hz<br />
2. CH 2 and 4 connections as standard voltage inputs.<br />
11<br />
CH2<br />
5<br />
6<br />
7<br />
<strong>PC3000</strong> - <strong>Installation</strong> Guide