12.01.2013 Views

PC3000 Complete Installation guide iss 12 - Elektro-Trading

PC3000 Complete Installation guide iss 12 - Elektro-Trading

PC3000 Complete Installation guide iss 12 - Elektro-Trading

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Status indication<br />

<strong>PC3000</strong> - <strong>Installation</strong> Guide<br />

Logic Output Module<br />

Output, 'health' and communications status indication are provided by means of<br />

indicators visible through the detachable connector/fascia assembly. The following<br />

assignment applies:<br />

Version 3 has introduced a change in the numbering of the Status Indication LED's<br />

Indicator Number Function Colour<br />

Version 2 Version 3<br />

1 F Fault Red<br />

2 C Comms Green<br />

3 R Run Green<br />

4 n/a<br />

5 1 Logic 1 Yellow<br />

6 2 Logic 2 Yellow<br />

7 3 Logic 3 Yellow<br />

8 4 Logic 4 Yellow<br />

9 5 Logic 5 Yellow<br />

10 6 Logic 6 Yellow<br />

11 7 Logic 7 Yellow<br />

<strong>12</strong> 8 Logic 8 Yellow<br />

13 9 Logic 9 Yellow<br />

14 10 Logic 10 Yellow<br />

15 11 Logic 11 Yellow<br />

16 <strong>12</strong> Logic <strong>12</strong> Yellow<br />

VERSION 2 VERSION 3<br />

1 2 3 4 F C R<br />

5 6 7 8 1 2 3 4<br />

9 10 11 <strong>12</strong> 5 6 7 8<br />

13 14 15 16 9 10 11 <strong>12</strong><br />

Note:<br />

The Logic Output module will indicate a fault under the following conditions:<br />

1. When the <strong>PC3000</strong> is in the reset mode i.e. program not running. It will clear<br />

when the <strong>PC3000</strong> is placed in the run state.<br />

2. If the module is placed in a slot which is not referenced by the <strong>PC3000</strong> program.<br />

3. A hardware fault.<br />

17-3

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!