PC3000 Complete Installation guide iss 12 - Elektro-Trading
PC3000 Complete Installation guide iss 12 - Elektro-Trading
PC3000 Complete Installation guide iss 12 - Elektro-Trading
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Status indication<br />
<strong>PC3000</strong> - <strong>Installation</strong> Guide<br />
Logic Output Module<br />
Output, 'health' and communications status indication are provided by means of<br />
indicators visible through the detachable connector/fascia assembly. The following<br />
assignment applies:<br />
Version 3 has introduced a change in the numbering of the Status Indication LED's<br />
Indicator Number Function Colour<br />
Version 2 Version 3<br />
1 F Fault Red<br />
2 C Comms Green<br />
3 R Run Green<br />
4 n/a<br />
5 1 Logic 1 Yellow<br />
6 2 Logic 2 Yellow<br />
7 3 Logic 3 Yellow<br />
8 4 Logic 4 Yellow<br />
9 5 Logic 5 Yellow<br />
10 6 Logic 6 Yellow<br />
11 7 Logic 7 Yellow<br />
<strong>12</strong> 8 Logic 8 Yellow<br />
13 9 Logic 9 Yellow<br />
14 10 Logic 10 Yellow<br />
15 11 Logic 11 Yellow<br />
16 <strong>12</strong> Logic <strong>12</strong> Yellow<br />
VERSION 2 VERSION 3<br />
1 2 3 4 F C R<br />
5 6 7 8 1 2 3 4<br />
9 10 11 <strong>12</strong> 5 6 7 8<br />
13 14 15 16 9 10 11 <strong>12</strong><br />
Note:<br />
The Logic Output module will indicate a fault under the following conditions:<br />
1. When the <strong>PC3000</strong> is in the reset mode i.e. program not running. It will clear<br />
when the <strong>PC3000</strong> is placed in the run state.<br />
2. If the module is placed in a slot which is not referenced by the <strong>PC3000</strong> program.<br />
3. A hardware fault.<br />
17-3