Configuration of a Replaced AS-Interface V2 Slave<br />

AS-Interface Configuration<br />

Automatic Configuration<br />

When a slave must be replaced, it can be automatically replaced with a slave with<br />

the same AS-Interface profile.<br />

This happens without the AS-Interface V2 Fieldbus having to stop, and without<br />

requiring any manipulation if the configuration mode’s Automatic addressing utility<br />

is active (see page 112).<br />

The replacement slave must initial have the address 0 (a new slave is usually factory<br />

set with a default address of 0), and the same profile as the slave it will replace. It<br />

will automatically assume the address of the replaced slave once installed, and will<br />

then be inserted into the list of detected slaves (LDS) and the list of active slaves<br />

(LAS).<br />

Manual Configuration<br />

Alternative options without automatic addressing are available:<br />

You can configure the replacement slave with the same address as the slave it<br />

will replace using the pocket programmer. As previously noted, the replacement<br />

must have the same product reference number and the same profile and subprofile<br />

of the slave to replace. It is thus automatically inserted into the list of<br />

detected slaves (LDS) and into the list of active slaves (LAS). This feature is<br />

available only if one, and not more than one, slave is inoperative.<br />

Change the address using the Scan For Devices window (see page 100).<br />

EIO0000000384 04/2012 121