AS-Interface Configuration<br />

Software Setup Principles<br />

At a Glance<br />

Setup Principle<br />

To respect the operating principles adopted in SoMachine software, the user should<br />

adopt a step-by-step approach for creating an AS-Interface application.<br />

The following table shows the software implementation phases of the AS-Interface<br />

Fieldbus.<br />

Mode Phase Description<br />

Logged out Declaration of module<br />

(see page 95)<br />

Declaration of slave<br />

devices (see page 116)<br />

Logged out<br />

or logged in<br />

<strong>Programming</strong><br />

(see page 120)<br />

Choice of the slot for the AS-Interface Master<br />

module TWDNOI10M3 on the expansion bus.<br />

Selection for each device:<br />

of its address on the bus<br />

of its profile<br />

<strong>Programming</strong> diagnostic functions with the<br />

IoDrvASI (see page 208) library.<br />

Logged in Transfer Transfer of the application to the controller.<br />

Diagnostic / Debugging<br />

(see page 116)<br />

Debugging the application with the help of:<br />

the SoMachine interface to display slaves (address,<br />

profile), and to assign them the desired addresses.<br />

NOTE: The declaration and deletion of the AS-Interface Master module on the<br />

expansion bus is the same as for other expansion modules. However, once two AS-<br />

Interface Master modules have been declared on the expansion bus, SoMachine<br />

will not permit any other AS-Interface Master modules to be declared.<br />

Considerations Prior to Connection<br />

You must ensure that all slaves have a unique address. In addition, the address of<br />

0 is reserved for automatic addressing mode. If there is a slave with an address of<br />

0 detected on the bus at start-up, the master will change to the offline phase and try<br />

to restart. You must ensure that all addresses are unique and that none are 0.<br />

WARNING<br />

UNINTENDED EQUIPMENT OPERATION<br />

Ensure that each slave has a unique address greater than 0.<br />

Failure to follow these instructions can result in death, serious injury, or<br />

equipment damage.<br />

94 EIO0000000384 04/2012