Modicon <strong>M238</strong> Logic Controller - Troubleshooting and FAQ<br />

Application program is not executed<br />

Possible causes:<br />

No POU declared in the task.<br />

Resolution:<br />

As POUs are managed by tasks, you must add at least one POU to a task:<br />

1. double click a task in the Devices window,<br />

2. click Add POU in the task window,<br />

3. select the POU you want to execute in the Input Assistant window and click OK.<br />

Possible causes:<br />

Application does not go to RUN state.<br />

One input is configured in RUN/STOP mode.<br />

Resolution:<br />

Use the input configured in RUN/STOP mode to run the application.<br />

CoDeSys Gateway does not start (CoDeSys Gateway SysTray icon is black)<br />

Possible cause:<br />

Connection during a long time.<br />

Resolution:<br />

If the CoDeSys Gateway SysTray icon is black (stopped):<br />

1. Open the task Manager,<br />

2. stop the Gatewayservice.exe, and start it again:<br />

Restart your computer or,<br />

in Control Panel, open Administrative Tools and Computer Management,<br />

in Service, double click CoDeSys Gateway,<br />

Click Start Service button.<br />

3. Check if the CoDeSys Gateway SysTray icon is red (running).<br />

Serial Line Communication is not Possible<br />

Possible causes:<br />

Communication settings are not identical between serial line devices.<br />

The controller is not operating correctly.<br />

EIO0000000384 04/2012 199