CANopen Configuration<br />

CANopen Operating Limits<br />

The Modicon <strong>M238</strong> Logic Controller CANopen master has the following operating<br />

limits:<br />

Maximum number of slave devices 16<br />

Maximum number of Received PDO (RPDO) 32<br />

Maximum number of Transmitted PDO (TPDO) 32<br />

UNINTENDED EQUIPMENT OPERATION<br />

WARNING<br />

Do not connect more than 16 CANopen slave devices to the controller<br />

Program your application to use 32 or fewer Transmit PDO (TPDO)<br />

Program your application to use 32 or fewer Receive PDO (RPDO)<br />

Failure to follow these instructions can result in death, serious injury, or<br />

equipment damage.<br />

EIO0000000384 04/2012 87